    I do know, man.

    even if it gets used before getting to the breaker

    It would be both added and consumed after the breaker. Like if you had a 10A solar system connected to a dual outlet, and a 10A space heater on the other outlet, there would only be 10A flowing through the outlet, and nowhere else in the system

    • BT_7274@lemmy.world
      link
      fedilink
      English
      arrow-up
      0
      ·
      2 months ago

      Yes, I was conceding that point. I was then worried about the actual romex in the walls entirely contained after the breaker. Are you able to pump as much power as you want at 15A on a 15A rated wire? There’s got to be some limit, right?